Wire gauge calculator
Enter the current, the one-way length of the cable, and your voltage, and I will recommend a copper AWG size and a fuse. The fuses are protecting the wire. That is their main job.
Part of: Electrical & Solar
Length is one-way (battery to the load, or source to the device). I double it for the round-trip path through the positive and negative cables. Use 3% voltage drop for most house circuits. The 10% option is only for non-critical loads where a little dimming or extra drop is acceptable.
Results
- Recommended wire
- -
- Voltage drop
- -
- Wire ampacity
- -
- Fuse or breaker
- -
How this works
I size the wire two ways, then pick the smallest AWG that passes both checks.
Voltage drop
Required circular mils = (K x current x 2 x one-way length in feet) / allowed voltage drop. K is 10.9 ohm-circular-mils per foot, a common copper constant at about 20 C. Allowed drop is 3% or 10% of system voltage (12, 24, or 48V). If you enter meters, I convert to feet first (1 m = 3.28084 ft).
Ampacity
The current also has to stay within the wire's ampacity. I use an ABYC E-11 style table for copper with 105 C insulation, in the form commonly published in marine references such as Blue Sea Systems. It is a planning table, not a reproduction of the standard. The engine-space column applies a 15% derate, which is how those tables treat engine rooms.
Ampacity figures I am using outside engine space: 18 AWG 20A, 16 AWG 25A, 14 AWG 35A, 12 AWG 45A, 10 AWG 60A, 8 AWG 80A, 6 AWG 120A, 4 AWG 160A, 2 AWG 210A, 1 AWG 245A, 1/0 285A, 2/0 330A, 3/0 385A, 4/0 445A.
Fuse or breaker
I recommend the smallest standard fuse or breaker that is at least the load current and no higher than the wire ampacity. That keeps the fuse as the weak point in the cable, not the insulation. Continuous loads are sometimes sized at 125% of operating current under NEC practice. If you are on a continuous load, enter that higher current so the wire and fuse both follow along. Always defer to the device manufacturer and a qualified electrician.
For the larger picture of where these cables sit in a van, see the camper van wiring diagram. For branch lighting circuits, I also have how to wire 12V LED lights.
This calculator is an estimate for education and planning, not a substitute for ABYC E-11, the National Electrical Code, or the instructions that come with your wire, fuse, and equipment. Insulation temperature, bundling, ambient heat, terminals, and fuse type all change the right answer. Follow ABYC or NEC as they apply to your build, and consult a qualified electrician before you size, install, or energize a circuit.